CT-V900-A

2-Door Controller

CT-V900-A

Overview

The CT-V900-A is the core component of every Centaur access control system. It integrates with the Centaur Server, hardware expansion modules, multi-purpose inputs, card readers, keypads, and outputs. Multi-controller systems are networked via the RS-485 communication bus or optionally via TCP/IP with the CA-ETHER-A. Its distributed database architecture allows each controller to make immediate decisions without needing to communicate with the Centaur server, ensuring high-speed, reliable performance.

Technical Specifications:

Features:

- Controls 2 doors (Reader In / REX Out) or 1 door (Reader In / Reader Out).

- Expandable to control up to 8 doors using the CA-A470-A expansion module.

- On-board card database capacity: 10,920 cards.

- 256 schedules.

- 256 access levels.

- 2048 event buffer.

- 16 on-board inputs (using ATZ 2R/3R).

- 2 on-board 12 VDC or 24 VDC field-selectable lock outputs.

- 2 on-board Form C dry contact relay outputs (N/O – N/C).

- Fully distributed database architecture (local access decisions).

- Flash firmware updateable via the Centaur Server.

- E-Bus technology allows add-on hardware modules to be located up to 1220m (4000ft) from the CT-V900-A.

- 2.5A switching power supply.

- Supports common Wiegand, Track 2 ABA (mag stripe), and BCD (keypad) formats.

- Easy maintenance with snap-off terminal blocks.

- Battery backup functionality (2 x 12V 7AH gel-type batteries).

- Lithium battery protection in case of complete power failure.

Communication

- RS-485 controller to expansion module network (9.6k or 19.2k baud).

- Connect modules up to 1220m (4000ft) from the controller.

- Plug and play technology.

- RS-232 support for communication with Centaur software via serial port, dial-up, or LAN.

Physical Specifications

- Cabinet size: 39 cm (15.5”) high x 33 cm (13”) wide x 10 cm (4”) deep.

- PCB dimensions: 24.5 cm (9.65”) x 20.2 cm (7.95”).

- Operating environment: 5°C to 55°C (41°F to 133°F).

Electrical Specifications

- Power input: 24 VAC, 75 VA or higher, 50/60 Hz transformer.

- Supply current: 2.5A maximum.

- Battery capacity: Two 12V DC, 7Ah acid/lead gel cell batteries.

Input Specifications

- Reader Inputs/Ports: 2.

- Keypad Inputs/Ports: 2.

- Multi-purpose Inputs: 16 (using ATZ 2R/3R).

Output Specifications

- 12/24 VDC lock outputs: 2.

- Relays: 2 Form C dry contact 5A/30VDC N.C/N.O.

- Reader Outputs: Six 50mA open collector outputs (Red/Green LEDs, Buzzer).

On-board Protection

- Auxiliary outputs: 2.5A (24VDC), 1A (12VDC & 5VDC) fuseless protection.

- AC protection: 5A fuse.

- Battery reversal: 7A fuse.